G5-HT AIR BREAK / LOAD BREAK SWITCH–12KV/24KV/36KV

TECHNICAL DATA
Rated Voltage 12KV 24kV 36KV
Rated Current 630A 630A 630A
Rated Insulation Level 28kV /75 kV 50kV / 125kV 70 kV / 170 kV
Rated Short time current 26.3 kA 26.3 kA 26.3 kA
Rated Frequency 50 Hz 50 Hz 50 Hz
Rated making current 65 kAp 65 kAp 65 kAp
Rated off load breaking 

capacity

16A 16A 16A
Capacitor Switching 

Current

25A 25A 25A
Number of Pole Three Three Three
Number of Breaks/Pole Single Single Single
SKU: SKU81 Categories: , , Tags: ,

Description

Indoor High-voltage Air Break / Load Break Switches are based on a modular principle, which is suitable for the power system of 3.6kV to 36kV. They represent an attractive solution as a key breaking current for application in enclosed Switchgear, Ring Main Unit and Compact Substations. In combination with current limiting fuses, Switch fuse unit ensure control over the full range of over load and short circuit currents. It is used for switching the transformers, Capacitors, protecting cables and overhead lines, etc. Load Break Switch has been tested at CPRI.

FEATURES

  • Switch can make and break the normal rated current.
  • Switch can withstand short circuit making current.
  • Mechanism has a quick make-make and quick-break feature and the speed of make and break being entirely independent of the operator.
  • The handle is trip free and a trip coil can be fitted if desired.
  • Switch is available with Earth Switch for cable earthing with safety interlocking.